Performance Analysis of Cooling Tower-Assisted Hybrid Ground-Coupled Heat Pump (HGCHP) System
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
 Title & Authors
Performance Analysis of Cooling Tower-Assisted Hybrid Ground-Coupled Heat Pump (HGCHP) System
Sohn, Byonghu; Lee, Doo-Young; Choi, Jae-Ho; Min, Kyong-Chon;
  PDF(new window)
 Abstract
This paper presents the measurement and analysis results for the performance of HGCHP system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from February 1, 2014 to February 28, 2015. Leaving load temperatures to building showed an average value of for cooling and for heating, respectively. From the analysis, the daily PF of hybrid GCHP system varied from 2.6 to 6.6 over the measurement period.
 Keywords
Hybrid Ground-Coupled Heat Pump System;Cooling Tower;Supplemental Heat Rejector;Performance Factor;
 Language
Korean
 Cited by
 References
1.
Kavanaugh, S., 1998, "A Design Method for Hybrid Ground-Source Heat Pump," ASHRAE Transactions, Vol. 104, pp. 691-698.

2.
Qi, Z., Gao, Q., Liu, Y., Yan, Y., and Spitler, J., 2014, "Status and Development of Hybrid Energy Systems from Hybrid Ground Source Heat Pump in China and Other Countries," Renewable and Sustainable Energy Reviews, Vol. 29, pp. 37-51. crossref(new window)

3.
Fan, R., Gao, Y. Hua, L., Deng, X., and Shi, J., 2014, "Thermal Performance and Operation Strategy Optimization for a Practical Hybrid Ground-Source Heat-Pump System," Energy and Buildings, Vol. 78, pp. 238-247. crossref(new window)

4.
Nguyen, H. V., Law, Y. L. E., Alavy, M., Walsh, P., Leong, W., and Dworkin, S., 2014, "An Analysis of the Factors Affecting Hybrid Ground-Source Heat Pump Installation Potential in North America," Applied Energy, Vol. 125, pp. 28-38. crossref(new window)

5.
Wang, S., Liu, X., and Gates, S., 2015, "Comparative Study of Control Strategies for Hybrid Gshp System in the Cooling Dominated Climate," Energy and Buildings, Vol. 89, pp. 222-230. crossref(new window)

6.
Sohn, B. and Kwon, H. S., 2014, "Performance Prediction on the Application of a Ground-Source Het Pump(GSHP) System in an Office Building," Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 26, No. 9, pp. 409-415. crossref(new window)

7.
Sohn, B., Choi, J. H., and Min, K. C., 2015, "Heating Performance of Geothermal Heat Pump System Applied in Cold Climate Region(Mongolia)," Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 27, No. 1, pp. 31-38. crossref(new window)

8.
Phetteplace, G. and Sullivan, W., 1998, "Performance of a Hybrid Ground-Coupled Heat Pump System," ASHRAE Transactions, Vol. 104, pp. 763-770.

9.
Hackel, S. and Pertzborn, A., 2011, "Effective Design and Operation of Hybrid Ground-Source Heat Pumps: Three Case Studies," Energy and Buildings, Vol. 43, pp. 3497-3504. crossref(new window)

10.
Pertzborn, A., Hackel, S., Nellis, G., and Klein, S., 2011, "Experimental Validation of a Ground Het Exchanger Model in a Hybrid Ground Source Heat Pump," HVAC&R Research, Vol. 17, pp. 1101-1114.