JOURNAL BROWSE
Search
Advanced SearchSearch Tips
A Special Protection Scheme Against a Local Low-Voltage Problem and Zone 3 Protection in the KEPCO System
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
 Title & Authors
A Special Protection Scheme Against a Local Low-Voltage Problem and Zone 3 Protection in the KEPCO System
Yun, Ki-Seob; Lee, Byong-Jun; Song, Hwa-Chang;
  PDF(new window)
 Abstract
This paper presents a special protection scheme, which was established in the KEPCO (Korea Electric Power Corporation) system, against a critically low voltage profile in a part of the system after a double-circuit tower outage. Without establishing the scheme, the outage triggers the operation of a zone 3 relay and trips the component. This sequence of events possibly leads to a blackout of the local system. The scheme consists of an inter-substation communication network using PITR (Protective Integrated Transmitter and Receiver) for acquisition of the substations` data, and under-voltage load shedding devices. This paper describes the procedure for determining the load shedding in the scheme and the experiences of the implementation.
 Keywords
KEPCO system;Local blackout;Low-voltage problem;Special protection scheme;Zone 3 protection;
 Language
English
 Cited by
1.
Methodology for Determining of Generator Operation Point for Ensuring Voltage Stability Against Generator Faults in Jeju-Haenam HVDC System,;;;;

Journal of Electrical Engineering and Technology, 2010. vol.5. 1, pp.54-60 crossref(new window)
2.
전력계통 운영조건을 고려한 발전기차단용 SPS 동작설정에 관한 연구,권한나;손혁진;국경수;양성채;

한국산학기술학회논문지, 2014. vol.15. 1, pp.411-417 crossref(new window)
1.
A Study on Setting SPS for Generator Tripping Action considering Operating Conditions of Power Systems, Journal of the Korea Academia-Industrial cooperation Society, 2014, 15, 1, 411  crossref(new windwow)
 References
1.
C. W. Taylor, Power System Voltage Stability, McGraw-Hill, 1994

2.
P. Kundur, Power System Stability and Control, McGraw-Hill, 1994

3.
M. Jonsson and J. E. Daalder, 'An adaptive scheme to prevent undesirable distance protection operation during voltage instability,' IEEE Trans. on Power Delivery, vol. 18, no. 4, Oct. 2003, pp. 1174-1180 crossref(new window)

4.
H. Song, B. Lee, and V. Ajjarapu, 'Determination of control strategies against undesired protective operation with respect to voltage collapse,' Bulk power system dynamics and control - VI, Cortian d'Ampezzo, Italy, Aug. 22-27, 2004

5.
D. Karlsson and X. Waymel, Eds., System protection schemes in power networks, Rep., CIGRE Task Force 38.02.19, June 2001

6.
C. W. Taylor, 'Concepts of undervoltage load shedding for voltage stability,' IEEE Trans. Power Systems, vol. 7, no. 2, April 1992, pp. 480-488

7.
C. Moors, D. Lefebvre, and T. Van Cutsem, 'Design of load shedding schemes against voltage instability,' in Proc. of 2002 IEEE PES Winter Meeting

8.
D. Karlsson, Eds., Protection against voltage collapse Rep., CIGRE Tast Force 34.08, 1998

9.
F. Dobraca, M. A. Pai, and P. W. Sauer, 'Relay margins as a tool for dynamical security analysis,' International Journal of Electrical Power & Energy Systems, vol. 12, no. 4, Oct. 1990, pp. 226-234 crossref(new window)