JOURNAL BROWSE
Search
Advanced SearchSearch Tips
Dynamic Characteristic Analysis of Electric Actuator for 1 kV/3.2 kA Air Circuit Breaker Based on the Three-link Structure
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
 Title & Authors
Dynamic Characteristic Analysis of Electric Actuator for 1 kV/3.2 kA Air Circuit Breaker Based on the Three-link Structure
Lee, Seung-Min; Kang, Jong-Ho; Kwak, Sang-Yup; Kim, Rae-Eun; Jung, Hyun-Kyo;
  PDF(new window)
 Abstract
In the present paper, a new type of electrical actuator, an electromagnetic force driving actuator (EMFA), applicable to air circuit breaker is developed and analyzed. Transient analysis is performed to obtain the dynamic characteristics of EMFA. The distribution of static magnetic flux is obtained using the finite element method. The coupled problems of electrics and mechanics governing equations are solved using the time-difference method. According to the interception rate of each contactor, investigation of the contactor spring load condition is conducted and applied to the threelink system. Comparisons of the dynamic characteristics of the three-link simulation and experimental data are performed.
 Keywords
Air circuit breaker;Electromagnetic force driving actuator;Finite element method Time difference method;
 Language
English
 Cited by
1.
Optimal Design of a Novel Permanent Magnetic Actuator using Evolutionary Strategy Algorithm and Kriging Meta-model,;;;

Journal of Electrical Engineering and Technology, 2014. vol.9. 2, pp.471-477 crossref(new window)
1.
Optimal Design of a Novel Permanent Magnetic Actuator using Evolutionary Strategy Algorithm and Kriging Meta-model, Journal of Electrical Engineering and Technology, 2014, 9, 2, 471  crossref(new windwow)
2.
Characteristic analysis and design of a novel permanent magnetic actuator for a vacuum circuit breaker, IET Electric Power Applications, 2013, 7, 2, 87  crossref(new windwow)
3.
Characteristics Analysis and Design of a Novel Magnetic Contactor for a 220 V/85 A, IEEE Transactions on Magnetics, 2013, 49, 11, 5498  crossref(new windwow)
 References
1.
W. S. Jackson, Vice President "The air circuit breaker 50 years of technology" Digital Object Identifier 10.1109/TEXCON. 1997

2.
E. Dullni, "A Vacuum Circuit-breaker with Permanent Magnetic Actuator for Frequent Operations", IEEE 18thInternational Symposium on Discharges and Electrical Insulation in Vacuum- Eindhoven, pp. 688-691, 1998.

3.
Xiong, Guangyu, and Yamada, "Dynamic analysis of a cylindrical moving-core linear oscillator actuator", Linear Drives for Industry Applications 95 Nagasaki, JAPAN, pp. 405-408, 1999.

4.
J.H. Kang, and H. K. Jung, "Development and Characteristic Analysis of New type Actuator, Electro Magnetic driven Force Actuator applicable to High Voltage Circuit Breaker" The Fifth International Symposium on Linear Drives for Industry Applications, 25-28 September 2005, pp. 383-386.

5.
W. Kim, S. Y. Kwak, J. Lee, D. Choi, H. K. Jung, K. Seong, and S. Hahn, "Design of HTS magnets for a 600 kJ SMES," IEEE Trans. on Appl. Supercond., vol. 16, no. 2, pp. 620-623, May 2006. crossref(new window)

6.
Ma Shaohua, and Wang jimei, "Research and Design of Permanent Magnetic Actuator for High Voltage Vacuum Circuit Breaker", IEEE XXth international Symposium on Discharges and Electrical Insulation in Vacuum, pp. 487-490, 2002