Investigation on Flashover Development Mechanism of Polymeric Insulators by Time Frequency Analysis
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
 Title & Authors
Investigation on Flashover Development Mechanism of Polymeric Insulators by Time Frequency Analysis
Muniraj, C.; Krishnamoorthi, K.; Chandrasekar, S.;
  PDF(new window)
 Abstract
This paper deals with the analysis of leakage current characteristics of silicone rubber insulator in order to develop a new condition monitoring tool to identify the flashover of outdoor insulators. In this work, laboratory based pollution performance tests are carried out on silicone rubber insulator under ac voltage at different pollution levels and relative humidity conditions with sodium chloride (NaCl) as a contaminant. Min-Norm spectral analysis is adopted to calculate the higher order harmonics and Signal Noise Ratio (SNR). Choi-Williams Distribution (CWD) function is employed to understand the time frequency characteristics of the leakage current signal. Reported results on silicone rubber insulators show that the flashover development process of outdoor polymer insulators could be identified from the higher order harmonics and signal noise ratio values of leakage current signals.
 Keywords
Polymer insulator;Flashover;Leakage current;Min-Norm;Choi-Williams distribution;
 Language
English
 Cited by
1.
Flashover Prediction of Polymeric Insulators Using PD Signal Time-Frequency Analysis and BPA Neural Network Technique,;;;

Journal of Electrical Engineering and Technology, 2014. vol.9. 4, pp.1375-1384 crossref(new window)
2.
Prediction of Flashover and Pollution Severity of High Voltage Transmission Line Insulators Using Wavelet Transform and Fuzzy C-Means Approach,;;;;

Journal of Electrical Engineering and Technology, 2014. vol.9. 5, pp.1677-1685 crossref(new window)
1.
Investigations of Accelerated Aged Polymeric Insulators Using Partial Discharge Signal Measurement and Analysis, Journal of Electrical Engineering and Technology, 2015, 10, 1, 299  crossref(new windwow)
2.
Prediction of Flashover and Pollution Severity of High Voltage Transmission Line Insulators Using Wavelet Transform and Fuzzy C-Means Approach, Journal of Electrical Engineering and Technology, 2014, 9, 5, 1677  crossref(new windwow)
3.
Flashover Prediction of Polymeric Insulators Using PD Signal Time-Frequency Analysis and BPA Neural Network Technique, Journal of Electrical Engineering and Technology, 2014, 9, 4, 1375  crossref(new windwow)
 References
1.
J.S.T. Looms, Insulators for High Voltages, IEE series, 1990.

2.
R.S. Gorur, E. A.Cherney and J. T. Burnham; Outdoor Insulators (Ravi S. Gorur, Inc., Phoenix, Arizona 85044, USA), 1999.

3.
Rebati Dass, "Grid disturbance in India on 2nd January 2001", No:196, pp 6-15, Electra, June 2001.

4.
CEA Enquiry Committee report of Grid incident of Northern region, 2007

5.
George G. Karady, Minesh shah, R.L. Brown, "Flashover mechanism of silicone rubber insulators used for outdoor insulation-I", IEEE Transactions on Power Delivery, Vol. 10, No.4, pp-1965-1971,1995.

6.
T.Suda, "Frequency characteristics of leakage current waveforms of an artificially polluted suspension insulator", IEEE Transactions on Dielectrics and Electrical Insulation, Vol.8, No.4,pp.705-709,Aug 2001 crossref(new window)

7.
B. Subba Reddy, G. R. Nagabhushana, "Study of Leakage Current Behaviour on Artificially Polluted Surface of Ceramic Insulator", Plasma Science & Technology, vo1.5, No.4, pp-1921-1926, (2003). crossref(new window)

8.
A. H. El-Hag, S. H. Jayaram and E. A. Cherney, "Fundamental and Low Frequency Harmonic Components of Leakage Current as a Diagnostic Tool to Study Aging of RTV and HTV Silicone Rubber in Salt Fog", IEEE Trans. Dielectr. Electr. Insul., Vol. 10, pp.128-136, 2003. crossref(new window)

9.
R. Sarathi and S. Chandrasekar, "Diagnostic study of the surface condition of the insulation structure using wavelet transform and neural networks", Electric Power Systems Research, Elsevier, Vol.68, pp.137-147, 2004. crossref(new window)

10.
Farhad Shahnia and Ghasem Ahrabian. "Different Characteristics of Artificially Polluted High Voltage Composite Insulators", Proceedings of the XIVth International Symposium on High Voltage Engineering, pp-1-6, August 25-29, 2005.

11.
M. T. Gencoglu, and M. Cebeci, " Computation of AC flashover voltage of polluted HV insulators using a dynamic arc model", European Transactions of Electrical power Vol, 2008

12.
C.Muniraj, S.Chandrasekar, "computation of Electric field and potential distribution pullulated composite insulator by finite element method" Proceeding of international conference, Electrical Energy systems & power Electronics in Emerging Economics ICEESPEEE 09, SRM university, India, pp 185-189,April 16th & 17th,2009.

13.
S. Chandrasekar, K. Krishnamoorthi, M. Panneerselvam and C.Kalaivanan, "Investigations on Flashover Performance of Porcelain Insulators under Contaminated Conditions", Proceedings of National Conference on Electrical Engineering and Embedded Systems, NCEEE'08, pp.112-116, 20-21 March 2008.

14.
S.Chandrasekar, and C.Kalaivanan "Investigations on Harmonic Contents of Leakage Current of Porcelain Insulator under Polluted Conditions", Proceedings of Fifteenth National Power Systems Conference (NPSC), pp.340-344, December 2008.

15.
C.Muniraj, S.Chandrasekar, "Analysis of Leakage Current on Polluted Polymer Insulator by High Resolution Spectrum Estimation method" Proceeding of Third International Conference on Power Systems, (ICPS) IEEE Kharagpur section, INDIA Dec2009.

16.
IEC 60507, Artificial pollution test on high voltage insualtors to be used on AC systems,1991.

17.
Tadeusz Lobos, Zbigniew Leonowicz, Jacek Rezmer, and Peter Schegner, "High-Resolution Spectrum-Estimation Methods for Signal Analysis in Power Systems", IEEE Transactions on Instrumentation and Measurement, Vol. 55, No. 1, pp. 219-225, February 2006 crossref(new window)

18.
H. I. Choi and W. J. Williams, "Improved time-frequency representation of multicomponent signals using exponential kernels," IEEE Trans.Acoust., Speech Signal Process., vol. 37, no. 6, pp. 862-9871, Jun. 1989. crossref(new window)

19.
Zbigniew Leonowicz, Tadeusz Lobos, and Tomasz Sikorski, "Time - Frequency Analysis of Complex Space Phasor in Power Electronics", IEEE Transactions on Instrumentation and Measurement, Vol. 56, No. 6, pp. 2395-2402, 2007. crossref(new window)

20.
R.S. Gorur, J. Montesinos, L. Varadadesikan, S. Simmons, and M. Shah, "A laboratory test for tracking and erosion resistance of HV outdoor insulation", IEEE Trans. Dielectr. Electr. Insul., Vol. 4, pp. 767-774, 1997. July 2001. crossref(new window)