JOURNAL BROWSE
Search
Advanced SearchSearch Tips
A Study on Fire Risk Assessment of a EPS room using Fire Simulation
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
 Title & Authors
A Study on Fire Risk Assessment of a EPS room using Fire Simulation
Ham, Eungu; Kim, Dongcheol; Lee, Changwoo;
  PDF(new window)
 Abstract
This study was conducted by utilizing simulation (FDS6) the fire characteristics of the flammable substances such as cable compartment of a small space in the EPS room type. In the partitioned space of a room EPS supply of oxygen does not facilitate the combustion of the upward-sloping curve, as in a standard fire curve is not observed. Simulation results in a situation where ventilation is limited to the heat release rate and smoke emission characteristics of the fire showed a complex and unstable form a repeating rise and fall. Fire time was longer than the fire load. Change in the smoke emission than the heat release rate is slow, but changes of the overall surface was found to exhibit affinity.
 Keywords
Small Spaces;Cable Fire;EPS;Simulation;FDS6;
 Language
Korean
 Cited by
1.
협소 거주공간 사고 재현을 위한 시뮬레이션 연구,;;;;;

한국재난정보학회 논문집, 2016. vol.12. 3, pp.210-218 crossref(new window)
 References
1.
NIST Special Publication 1018-1 Sixth Edition(2015), "Fire Dynamics Simulator Technical Reference Guide", The National Institute of Standards and Technology

2.
Sam-Kew Roh, Dong-Cheol Kim, Eun-Gu Ham(2012), "The study of fire suppression capability of low pressure water-mist system for wooden cultural properties", Journal of the Korea Society Disaster Information Vol. 8 No.4 pp 401-410

3.
MPSS(Ministry of Public Safety and Security). (2014). http//www.mpss.go.kr "Statistics of Fire Status"

4.
LAPP GROUP PRODUCTS. (2015). Appendix T27 : Fire Load Calculation of Cables. LAPP GROUP, Canada