 Abstract
The ELCB(: Earth Leakage Circuit Breaker) is the only way being used to prevent accidents from happening caused by electrical disaster. However, the existing ELCB has a limit to prevent damages to life and property due to a electric fire and a human body electric shock caused by the resistive leakage current, because of detecting the total leakage current in the block range of 15mA~30mA. It also has problems such as reduced productivity and reliability due to malfunctions by capacitive leakage currents. In this study, we have implemented the algorithm for the resistive leakage current detection technique and developed the resistive leakage current detection module based on a MSP430 processor, 16bit signal processor and this module can be operated in a desired block threshold within 0.03 seconds as specified in KS C 4613.
 Keywords
ELCB;Resistive Leakage Current;Capacitive Leakage Current;Active Leakage Current Detection;MSP430 Processor;
 Language
Korean
 Cited by
 References
1.
Y. Han and D. Kim, "The development of a android application for intelligent outlets," J. of the Korea Institute of Electronic Communication Sciences, vol. 9, no. 4, 2013., pp. 447-452.

2.
K. Ban, K. Yoon, J. Park, M. Nam, and N. Kim, "The design of control algorithm for leakage current detection and blocking," Int. and Control Proc., 2003, pp. 417-420.

3.
C. Shoi, H. Kim, and D. Kim, "Flame Spread and Damaged Properties of RCD Cases by Tracking," IEEE Trans. PE, vol. 127, no. 1, 2007, pp.321-326 crossref(new window)

4.
Korea Industrial Standards, KS C 4613, Korea Industrial Standards Association, 2006.

5.
IEC 61009-1 : Residual current operated circuit-breakers with integral over current protection for household and similar uses(RCBO's) : General rules, 2002.

6.
Y. Go, "The Arc Fault Determination Method for the Electric Fire Prevention," J. of the Korea Institute of Electronic Communication Sciences, Vol. 3, No. 4, pp. 260-265, 2008.

7.
Texas Instruments, "MSP430x4xx Family User's Guide," Texas Instruments Document, pp. 1-946, 2013.

8.
Y. Han, "The development of a Leakage Current Detection Module for outlets," J. of the Korea Institute of Electronic Communication Sciences, vol. 9, no. 4, 2013, pp. 447-452.

9.
S. Ham, S. Han, and C. Go, "The New Earth Leakage Breaker Operating with Resistive Leakage Current," J. of the Korean Institute of Electrical Engineerings, vol. 57, no. 2, 2008, pp. 198-207.