JOURNAL BROWSE
Search
Advanced SearchSearch Tips
Design of the Heat Exchanger in Pool Water Management System of a Research Reactor and Estimation of the Pool Water Temperature Using CFD
facebook(new window)  Pirnt(new window) E-mail(new window) Excel Download
  • Journal title : Journal of Energy Engineering
  • Volume 25, Issue 2,  2016, pp.45-51
  • Publisher : The Korea Society for Energy Engineering
  • DOI : 10.5855/ENERGY.2016.25.2.045
 Title & Authors
Design of the Heat Exchanger in Pool Water Management System of a Research Reactor and Estimation of the Pool Water Temperature Using CFD
Jeong, Namgyun;
  PDF(new window)
 Abstract
The pool water management system, which is installed for purification of the coolant in the pools and the primary cooling system of a research reactor, removes the decay heat from the reactor core when the primary cooling system stops. It also removes the heat generated from the irradiated objects in the service pool and the spent fuels in the spent fuel storage pool to keep the temperature of the pools within a limited value. In this study, the heat exchanger of the pool water management system is designed by CFD method using a commercial code Flowmaster, and the temperature of the pools is estimated along the time to conclude the design and operation method of the pool water management system.
 Keywords
Research Reactor;Pool Water Management System;Plate-type Heat Exchanger;CFD;
 Language
Korean
 Cited by
 References
1.
김석권: "열교환기 설계와 열적 계산법", 신기술, (2000)

2.
Flowmaster V7: "New user training", version 10

3.
Icleanu, D. L., Prisecaru, I., Jianu, I. N.: "Cooling the intact loop of primary heat transport system using Shutdown Cooling System in case of LOCA events", EPJ Nuclear Sci. Technol, Vol. 1, 13, (2015) crossref(new window)

4.
윤정의: "가스분사 방식 LPG 엔진의 연료공급시스템 관로 유동해석", 대한기계학회논문집 B권, 제35권, 제10호, 1019-1024, (2011)

5.
Kakac, S and Liu, H.: "Heat Exchangers: Selection, Rating, and Thermal Design", CRC press, Florida, 380-381, (2002)

6.
Martin, H.: "A theoretical approach to predict the performance of chevron-type plate heat exchangers", Chemical Engineering and Processing, Vol.35, 301-310, (1996) crossref(new window)

7.
Metally, H. M. and Manglik, R. M.: "Enhanced heat transfer due to cuvature-induced lateral vortices in lamina flows in sinusoidal corrugate-plate channels", Heat and Mass Transfer, Vol.47, 2283-2292, (2004) crossref(new window)

8.
Fernandes, C. S., Dias, R. P., Nobrega, J. M., Maia J. M.: "Friction factors of power-law fluids in chevrontype plate heat exchangers", Journal of Food Engineering, Vol.89, 441-447, (2008) crossref(new window)

9.
Naik, V. R. and Matawala, V. K.: "Experimental Investigation of single phase Chevron Type Gasket Plate Heat Exchanger, International Journal of Engineering and Advanced Technology", Vol.2, 362-369, (2013)

10.
Asadi, M. and Khoshkhoo, R. H.: "Effects of Chevron Angle on Thermal Performance of Corrugated Plate Heat Exchanger", International Journal of Engineering Practical Research, Vol.3, 8-12, (2014) crossref(new window)

11.
장진아, 김원민, 김봉환: "진단시험기반 기기냉각해 수계통 운전여유도 분석", 한국전력기술주식회사 발간자료, 2013