A Study on the Frequency Bias Setting of the AGC based on Frequency Response in Korea

전력계통 주파수응답 실적 기반의 국내 AGC 주파수 바이어스 설정치 산정에 관한 연구

Kang, Bo-Ram;Kwon, Han-Na;Kook, Kyung-Soo
강보람;권한나;국경수

  • Received : 2015.05.04
  • Accepted : 2015.06.29
  • Published : 2015.07.01

Abstract

This paper presents Frequency Bias setting for the adequate AGC(Automatic Generator Control) operation based on the frequency response of power system in Korea. AGC frequency control recovers the frequency up to 60Hz following a primary control when the frequency suddenly drops due to a fault in power system. AGC can compensate an appropriate amount of generation by calculating ACE(Are Control Error) from the frequency deviation with the AGC frequency bias set from the actual frequency response in power systems. An appropriateness of the proposed AGC bias setting is verified through case studies employing the simulation model.

Keywords

Frequency bias;AGC(Automatic Generator Control);Power system frequency