800kV 차단부의 무부하 압력상승 측정

Measurement of Pressure-Rise at No-Load in 800kV Model Interrupter

  • 장기찬 (한국전기연구소, 개폐장치연구팀) ;
  • 송기동 (한국전기연구소, 개폐장치연구팀) ;
  • 정진교 (한국전기연구소, 개폐장치연구팀) ;
  • 송원표 ((주)효성중공업 기술연구소) ;
  • 김정배 ((주)효성중공업 기술연구소) ;
  • 박경엽 (한국전기연구소, 개폐장치연구팀) ;
  • 신영준 (한국전기연구소, 개폐장치연구팀)
  • 발행 : 1995.11.18

초록

The variations of cold gas properties such as density, pressure, temperature and velocity which are dependent each other are closely related with the dielectric recovery of an interrupter. So, the pressure-rises at no-load in the puffer cylinder and in front of fixed arcing contact of 800kV model interrupter were measured experimentally using pressure transducers of strain gage type and semiconducting type, respectively. The maximum value of pressure-rise in the puffer cylinder increased almost linearly from 7.6 bar at the minimum operated pressure to 9.7 bar at the maximum operated pressure, while the pressure-rise in front of fixed arcing contact was independent with the operated pressure. The measured values will be utilized in verifying the self-developed cold flow analysis program and as an input of commercialized CFD program package.