A Possible diagnostic method of cable system using SI-PD measurement

충격파-부분방전(SI-PD) 시험방법을 이용한 케이블 진단에 관한 기초 연구

  • Published : 1996.07.22

Abstract

In this paper, applicability of SI-PD(switching impulse - partial discharge) testing method was put on an attempt as a newly proposed diagnostic method for the underground distribution power cable system in Korea. For this purpose, SI-PD testing equipment was designed, and tests were performed using artificial needle-type defects integrated into the 22.9 kV CN/CV cables in drder to prove its reliability. As a result, arc noises, generated from spark gap, were considerably decreased by use of a pneumatic switch immersed into oil, and artificial needle-type defects were well detected with impulse voltage level under $2U_0$. These results imply that it is likely possible to apply SI-PD measurement method as a the nondistructive test for the 22.9 kV CN/CV cable system in Korea.