A Study on Suggestion of Insulating Oil Ageing Degree in Pole-Transformer by Absorbance

흡광도법에 의한 주상변압기 절연유의 열화판정기준 설정에 관한 연구

  • Published : 1996.07.22

Abstract

In this paper the criteria for insulating oil condition of pole transformer were suggested by applying the UV-Visible spectrophotometric method. Ageing of insulating oil caused the change in absorbances of oil os well os the deterioration of electrical properties of oil. By comparing the electrical properties such as $tan{\delta}$ and breakdown voltage with the UV-Visible absorbances of oil, criteria for absorbance values determining oil condition were established. This UV-Visible spectrophotometric method might be applied in ageing analysis of oil and be expected to replace the current method.

Keywords