Thermal Analysis of Mica/Epoxy Composites used In Generator Stator Windings

발전기 고정자 권선에서 사용되는 마이카/에폭시의 열적 분석

  • Published : 1997.04.01

Abstract

The thermal impact of mica/epoxy paper(130${\mu}{\textrm}{m}$) is investigated using XRD, DSC and TGL X-ray diffraction(XRD) analysis was performed to know the position and structure of mica crystal in insulation materials. A differential scanning calorimeter(DSC) was used to measure glass transition temperature and excess enthalphy of the composite materials that had been subjected to thermal aging. The glass transition temperature(T$_{g}$) measured by DSC is observed at 95.43$^{\circ}C$ and 113.43$^{\circ}C$, respectively. The T$_{g}$ also increases with increased aging time. Measurements performed by TGA(thermogravimetric analysis) have showed that weight loss profile of sound specimens are lower than those aged.ged.

Keywords