High Frequency Impedance Calculation of Grounding Meshes Installed at Power Substations

전력용 변전소에 설치된 메쉬 접지망의 고주파 임피던스 계산

  • Han, Poong (Power Engineering Research Institute, Korea Power Engineering Co.) ;
  • Choi, Chang-Hyek (Power Engineering Research Institute, Korea Power Engineering Co.)
  • 한풍 (한국전력기술주식회사 전력기술개발연구소) ;
  • 최창혁 (한국전력기술주식회사 전력기술개발연구소)
  • Published : 1998.07.20

Abstract

The ground potential rise generated by the switching surge or lightning stroke may be dangerous to personnel and cause damage to electronic control parts. For a first step to the transient performance analysis. high frequency impedances of grounding grids have been calculated and discussed. Grounding grids include 7 square grids from $10m{\times}10m$ to $80m{\times}80m$. The high frequency current was injected into the center and a corner of the grounding grid. The calculation results indicate that the impedance of the grounding grid is significantly influenced by frequency and the point of injection of the current. and the effective radius of a large grounding grid may be represented in $15{\sim}20m$.

Keywords