The Simulated study of different partial discharge sources in GIS

모의된 GIS에서 발생하는 부분방전에 관한 연구

  • Published : 1998.07.20

Abstract

The paper presents experimental results of Partial Discharge(PD) in Gas Insulated Switchgear(GIS), obtained using a computer-aided PD measurement system. Different discharge sources are simulated and identified. These included internal, interface, surface and protrusion. For internal discharge, it showed symmetrical discharge type between positive and negative cycle. Interface discharge showed smaller number and higher peak than internal discharge but symmetrical discharge as well. For surface discharge, it showed small number and high peak in positive half cycle but large number and low peak in negative half cycle. For protrusion discharge, small number and high peak of discharge were shown only in negative half cycle.

Keywords