A Finite Element Analysis on the Influence of Floating Shield of a Vacuum Interrupter to the Insulation

진공 인터럽터의 차폐판이 절연에 미치는 영향의 유한요소해석

  • Published : 1998.11.01

Abstract

This study should investigate to what extent the electric field of a vacuum interrupter might be influenced by the electric potential of floating arc shield. The electric potentials of floating shield and electric fields of a vacuum interrupter are analysed by a finite element method against variation of gap distances from 1mm to 12mm. The electric potentials of floating shield was increased with the gap distance, which is because the relative position of shield is closer to fixed contact so that the capacitance distribution inside interrupter is varied. The calculated results show that the maximum value of electric field of a vacuum interrupter with floating shield is nearly same to that without shield at shorter gap distance(below 5mm), however at larger gaps a significant increment of electric field is achieved in interrupter with shield companying with model without shield, which is due to the influence of charged floating shield.

Keywords