A Measurement and Diagnosis for Resistive Leakage Current of ZnO Arrester Element

ZnO 피뢰기 소자의 저항분 누설전류 측정 및 분석

  • Lee, Bok-Hee (Dept of Electrical Engineering, Inha University) ;
  • Kang, Sung-Man (Dept of Electrical Engineering, Inha University) ;
  • Park, Jin-Woo (Dept of Electrical Engineering, Inha University)
  • 이복희 (인하대학교 전기공학과) ;
  • 강성만 (인하대학교 전기공학과) ;
  • 박진우 (인하대학교 전기공학과)
  • Published : 1999.07.19

Abstract

This paper describes a new measurement method of resistive current and the technique of deterioration diagnosis for ZnO element. The consequence of current increasing (resistive current) with time is the eventual attainment of a state of thermal instability that may lead to arrester failure. So, it is very important to measure a leakage current of ZnO arrester installed at on-state. For the high-precision and more reliability, an iron core, which has a very high relative permeability, was used for increasing detection sensitivity, and we also used the personal computer for the data storage and program and analysis. And we have verified the reliability and performance of the sensing device through several laboratory tests.

Keywords