A Study on the Soil Resistivity and the Variation with Lapse of Time for Ground Rods

대지저항률과 접지극의 경년변화에 관한 연구

  • Han, Ki-Boong (Korea Electrical Safety Co., Electrical Safety Laboratory Research Institute) ;
  • Choi, Chung-Seog (Korea Electrical Safety Co., Electrical Safety Laboratory Research Institute) ;
  • Kim, Sham-Su (Korea Electrical Safety Co., Electrical Safety Laboratory Research Institute) ;
  • Jung, Se-Joong (Korea Electrical Safety Co., Electrical Safety Laboratory Research Institute) ;
  • Lee, Sang-Ick (Korea Electrical Safety Co., Electrical Safety Laboratory Research Institute)
  • 한기붕 (한국전기안전공사 전기안전시험연구원) ;
  • 최충석 (한국전기안전공사 전기안전시험연구원) ;
  • 김삼수 (한국전기안전공사 전기안전시험연구원) ;
  • 정세중 (한국전기안전공사 전기안전시험연구원) ;
  • 이상익 (한국전기안전공사 전기안전시험연구원)
  • Published : 1999.07.19

Abstract

This paper deals with the seasonal variation of soil resistivity and the special characteristic for ground rods by lapse of time. The ground resistance was changed by humidity, temperature of earth and earth resistance. In this experiment, we studied the resistivity during the period from June 1995 to May 1996 by the soil and the corrosion of the ground rods. As a result, the soil resistivity during the period are appeared minimum in summer and maximum in winter. The loss in weight of Fe rod appeared higher than Cu, Al, Cu-Zn, and St. In the lapse of time, Fe rod was reduced 1.2 % later two years and 1.95 % later three years in weight. Cu rod was defected oxygens of 14.7 % later two years and 30.3 % later three years by EDX.

Keywords