Failure Analysis of Porcelain Suspension Insulators for Distribution Line

배전용 자기제 현수애자의 고장 분석

  • Published : 1999.05.01

Abstract

The paper provides the results of failure analysis for the porcelain suspension insulators. The comparisons of characteristics were made as a function of failed and unfailed isulators which had been used in real distribution line. This paper also described the failure modes which could be occurred in the fields. The cracks inside cap were detected though measuring the resistance or the leakage current. The ratio of open porosity was calculated from the Archimedes Method. The failure analyses of porcelain suspension insulators were conducted from the various analysis method.