초록

This paper deals with the dynamic property of ground overvoltage relay in large turbine generator. Relay operation is based on detecting the fundamental voltages originating from the generator. Calculations of fault voltage and current are reviewed for the neutral ground resistance. The frequency, ampitude and waveform of individual harmonics were measured using power quality analyzer and memory hi-corder at the secondary side of ground potential transformer. The ac and dc high-potential tests were applied to evaluate the condition of generator, main and auxiliary transformer, isolated phase bus, potential transformer, surge capacitor and arrester.