Off-Line and On-Line Partial Discharge Properties of Large Turbine Generator

대용량 터빈발전기 고정자 권선의 정지중 및 운전중 부분방전 특성

  • Published : 2000.07.17

Abstract

Off-line and on-line partial discharges were measured on a 828MVA, 22kV and direct hydrogen-cooled large turbine generator. Partial discharge tests were conducted using digital partial discharge detector(PDD) and turbine generator analyzer(TGA). PDD and TGA showed that off-line partial discharge pattern seems to be very, similar to that found with on-line. Most of the partial discharge is originating with the stator slot in the three phases. As the partial discharge activity is very low, the stator insulation condition of this generator is very good.