변압기의 권선변형 검증을 위한 LVI 시험기 개발

The Development of LVI Tester for WInding Deformation Measurement in Power Transformers

  • 발행 : 2000.11.01

초록

The assessment of the condition of a transformer winding which is suspected of having suffered short circuit damage can be difficult. Conventional test such as winding resistance, magnetisation current or insulation resistance will only detect damage if a permanent electrical fault exists. Visual inspection of windings necessitates the removal of oil and in many cases only a very small proportion of the winding can be seen. We describe the characteristics. As the front rise time of recurrent-surge generator pulse less than 1000ns and the peak value of pulse is about 500V, we have the good results of detecting winding deformation in the LVI test of transformers.