Application of Lookup Table Technique with PID Controller for East Flow Ratio Response

  • Klaynil, P. (Faculty of Engineering King Mongkut's Institute of Technology Ladkrabang) ;
  • Pannil, P. (Faculty of Engineering King Mongkut's Institute of Technology Ladkrabang) ;
  • Chaikla, A. (Faculty of Engineering King Mongkut's Institute of Technology Ladkrabang) ;
  • Julsereewong, P. (Faculty of Engineering King Mongkut's Institute of Technology Ladkrabang) ;
  • Tirasesth, K. (Faculty of Engineering King Mongkut's Institute of Technology Ladkrabang)
  • Published : 2000.10.01

Abstract

The flow ratio in the industrial process is usually accomplished by using PID controller with series type ratio. But always the large overshoot and a long rise time may be achieved from this conventional control. These problems are involved to the inexact flow ratio control. In order to avoid this poor performance. the paper presents a designing of the two controller modes for the flow ratio plants. This proposed controller combine the lookup table technique and the well-known PID controller to obtain the fast response and low overshoot of flow ratio control. The PID controller mode will be operated when the flow ratio reaches the preset value while the lookup table technique mode is applied for initial operation. The data in tile table is calculated by the valve sizing equation and convened to the valve position control signal. The experimental results show that the transient and steady state responses of the control systems using the proposed technique can be efficiently obtained when compared with tile conventional controller.