Performance Prediction of Heat Exchanger for Waste Heat Recovery from Humid Flue Gases

습증기를 포함한 연소가스의 폐열회수를 위한 열교환기 성능 예측

  • 정동운 (한국과학기술원 대학원 기계공학과) ;
  • 이상용 (한국과학기술원 기계공학과) ;
  • 이한주 (한국과학기술원 대학원 기계공학과)
  • Published : 2000.04.20

Abstract

A simulation program using the mass transfer correlation was constructed to analyze 1-D simplified condensing flow across the tube bank. Higher efficiency was anticipated by reducing the flue gas temperature down below the dew point where the water vapor in the flue gas is condensed at the surface of the heat exchanger; that is, the heat transfer by the latent heat is added to that by the sensible heat. Thus, there can be an optimum operating condition to maximize the heat recovery from the flue gas. The temperature rises of the flue gas and the cooling water between the inlet and the outlet of the tube bank were compared with the experimental data reported previously. The predicted results agree well with the experimental data. Using this simulation program, the parametric studies have been conducted fur various operating conditions, such as the velocities and temperatures of the vapor/gas mixture and the cooling water, the number of the rows, and the conductivity of the wall material.

Keywords