차분을 이용한 변류기 포화 검출 알고리즘의 저역통과 필터의 영향 분석

Performance Analysis on a Low Pass Filter of a CT Saturation Detecting Algorithm Using Difference of the Secondary Current

  • 강용철 (전북대학교 전자정보공학부) ;
  • 옥승훈 (전북대학교 전자정보공학부) ;
  • 윤재성 (전북대학교 전자정보공학부) ;
  • 김대성 (전북대학교 전자정보공학부)
  • 발행 : 2001.07.18

초록

This paper presents performance analysis on a low pass filter of a CT saturation detecting algorithm using difference. At the instants of beginning/end of saturation, the shapes of the secondary current are changed significantly though secondary currents are continuous. At the instants, the second-order or third-order difference of the secondary current has big values because of discontinuity of the first order difference. Thus, the third difference of the current is used to detect the beginning/end of CT saturation. An antialiasing low pass filter removes high frequency components and causes phase lag. A CT saturation detecting algorithm using difference of CT secondary currents is affected by the low pass filter. The algorithm is tested with cutoff frequencies of the filter for the two sampling rates of 64[S/C] and 32 [S/C]. The results of various test cases indicate satisfactory performance of the algorithm.

키워드