A Study on the Reduction of Sheath Circulating Current in Underground Transmission Systems

지중송전계통의 시스순환전류 저감에 관한 연구

  • Published : 2001.11.16

Abstract

Sheath circulating current results from the change of sheath mutual impedance which is caused by unbalanced cable system, and different section length between joint boxes. If circulating over current flows in sheath, it produces much sheath loss which reduces the transmission capacity. And also such large sheath current influences severely on the operator. Recently, large sheath circulating current was partially measured in underground cable system of KEPCO. Accordingly, actual schemes to reduce sheath circulating over current is urgently required for installed cable system as well as newly-constructing cable system. This paper describes the analysis of sheath circulating current and various schemes to reduce the large circulating current in case of operating cable system using EMTP/ATPDraw. And also, possible schemes are proposed through a detailed analysis regarding cable systems by considering various electrical and environmental factors. It is evaluated that the proposed reduction schemes can be effectively applied to reduce the large sheath circulating over current with the minimized electrical problems.

Keywords