A Study on The Development and Function Test of Digital Transformer Protection Relay Using The Induced Voltage

유기전압비를 이용한 디지털형 변압기 보호계전기 개발 및 성능시험에 관한 연구

  • Published : 2001.11.16

Abstract

The transformer role is very important in power system operation and control; also its price is very expensive. Therefore many kinds of the efforts for transformer protection have been executed. So for as, current differential relay(87) has been mainly used for transformer protection. But current differential relaying method has several troubles as followings. Differential current can be occurred by transformers inrush current between winding1 and winding2 of transformer when transformer is initially energized. Also harmonic restrained element used in current differential relaying method is one of the causes of relays mal-operation because recently harmonics in power system gradually increase by power switching devices(SVC, FACTS, DSC, etc). Therefore many kinds of effort have been executed to solve the trouble of current differential relay and one of them is method using ratio of increment of flux linkages(RIFL) of the primary and secondary windings. This paper introduces a novel protective relay for power transformers using RIFL of the primary and secondary windings. Novel protective relay successfully discriminates between transformer internal faults and normal operation conditions including inrush and this paper includes real time test results using RTDS(Real Time Digital Simulator) for novel protective relay. A novel protective relay was designed using the TMS320C32 digital signal processor and consisted of DSP module. A/D converter module, DI/DO module, MMI interface module and LCD display module and developed by Xelpower co., Ltd.