A Study on the Digital Distance Relaying Algorithm Using Wavelet Transform in Combined Transmission Line with Underground Power Gables

웨이브렛 변환을 이용한 혼합송전계통에서의 디지털 거리계전 알고리즘에 관한 연구

  • Published : 2001.11.16

Abstract

Distance relay is tripped by the line impedance calculated at the relay point. Accordingly the accurate operation depends on the precise calculation of line impedance. Impedance can be accurately calculated in case of overhead line. However, in case of power cables or combined transmission lines, impedance can not be accurately calculated because cable systems have the sheath, grounding wires, and cable cover protection units (CCPUs). There are also several grounding systems in cable systems. Therefore, if there is a fault in cable system, these terms will severely be caused much error to calculation of impedance. Accordingly the proper compensation should be developed for the correct operation of the distance relay. This paper presents the distance calculating algorithm in combined transmission line with power cable using wavelet transform. In order to achieve such purpose, judgement method to discriminate the fault section in both sections was proposed using db1 coefficient summation. And also, error compensation factor was proposed for correct calculation of impedance in power cable.

Keywords