라인-디퓨저의 ADPI특성에 관한 연구

ADPI Characteristics of a Line-Diffuser

  • 이재헌 (한양대학교 공과대학 기계공학부) ;
  • 조영진 (한양대학교 대학원 기계공학과) ;
  • 강석윤 (한양대학교 대학원 기계공학과) ;
  • 오명도 (서울시립대학교 공과대학 정밀기계공학과)
  • 발행 : 2001.11.01

초록

It is difficult to apply a conventional selection guide for diffusers when the diffuser is installed in a perimeter zone, because the ADPI(Air Diffusion Performance Index) vs. T/L(Throw/Length) curve listed in conventional guide does not consider the perimetric heating load. The objective of this study is to evaluate the effect of the perimetric heating load on the ADPI and to propose a selection guide for proper diffuser when perimetric heating load exists. The velocity and temperature distributions and the ADPI value are obtained numerically with various heat load ratios and air flow rates. The ADPI values by numerical result were compared with existing experimental data to verify the method for evaluation of ADPI proposed in present study. In case of a high side wall diffuser, the ADPI decreased with increases of the flow rate on every heat load ratio of present study except 0.75. Also, the ADPI vs. T/L curves have been proposed for the heat load ratios of 0.25, 0.5, 0.75 to guarantee comport thermal environment when diffusers are installed in perimeter zone.