The Study on Correction of Protective Relaying Set Value for the Power Electric Network Paralleled with Wind Farm

풍력전단지의 계통 연계 운전에 따른 보호 계전기 설정치 정정에 관한 고찰

  • Jang, Sung-Il (Kangwon National University/Next-Generation Power Technology Center) ;
  • Choi, Don-Man (Kangwon National University/Next-Generation Power Technology Center) ;
  • Choi, Jeong-Hwan (Kangwon National University/Next-Generation Power Technology Center) ;
  • Kim, Kwang-Ho (Kangwon National University/Next-Generation Power Technology Center) ;
  • Oh, Jong-Youl (Kangwon National University/Next-Generation Power Technology Center) ;
  • Kim, Joo-Yearl (KEPCO)
  • 장성일 (강원대학교 전기전자정보통신공학부/차세대전력기술연구센터) ;
  • 최돈만 (강원대학교 전기전자정보통신공학부/차세대전력기술연구센터) ;
  • 최정환 (강원대학교 전기전자정보통신공학부/차세대전력기술연구센터) ;
  • 김광호 (강원대학교 전기전자정보통신공학부/차세대전력기술연구센터) ;
  • 오종률 (한국전력공사) ;
  • 김주열 (한국전력공사)
  • Published : 2002.07.10

Abstract

Wind farm paralleled with electric power network can supply the power into a power network not only the normal conditions, but also the fault conditions of distribution network. If the fault happened in the power line with wind farm, the fault current level measured in a relaying point might be lower than that of distribution network without wind turbine generator. Consequently, it is difficult to detect the fault happened in the distribution network connected with wind generator. This paper describes the influence of wind turbine generator on the protective relaying system for detecting the fault occurred in a power line network. Simulation results shows that the fault current depends on the fault impedance, location, and the capacity of wind farm and distribution network load.