XLPE 특고압 전력케이블의 절연 진단

Diagnostic Test of XLPE Ultra High Voltage Electric Power Cable

  • 발행 : 2002.05.17

초록

A diagnostic test of 15.4kV cross-linked polyethylene(XLPE) ultra high voltage power cables from generator in the Soyanggang hydro electric power plant was conducted over 3 months, beginning April 2001. According to the results, in the case of the power cables from generator 1, there was little possibility of proceeding rapid1y to failure or defect because the data from diagnosis doesn't indicate any failure, deterioration or partial discharge. However, in the case of the power cables from generator 2, the. polarization index show a slight abnormal condition of the insulator that is not severe, and the deterioration was also identified as not severe. However, the partial discharge had an abnormal condition which was severe.

키워드