전력케이블 열화진단기법의 현장적용

Field Application of Power Cable Diagnosis System

  • 김주용 (한전 전력연구원 송변전기술그룹) ;
  • 한재홍 (한전 전력연구원 송변전기술그룹) ;
  • 송일근 (한전 전력연구원 송변전기술그룹) ;
  • 김상준 (한전 전력연구원 송변전기술그룹) ;
  • 이재봉 (한전 전력연구원 송변전기술그룹) ;
  • 오재형 (한전 전력연구원 송변전기술그룹)
  • 발행 : 2002.05.17

초록

In order to prevent the failures of underground distribution power cables we need to measure insulation condition in the field. Until now we used DC high voltage as a power source for the cable diagnosis but it was not proper method to the XLPE insulation cables because DC high voltage can affect sound insulation and can't diagnose exactly insulation degradation. For these reasons we imported isothermal relaxation current measurement system called by KDA-1 from germany but it's reliability did not proved in our URD cables. DC voltage decay measurement system was developed by domestic company but they don't have field experience. In this paper we tried to prove reliability of these two systems in the field. Through the field diagnosis and Ac breakdown test the two systems showed similar results.

키워드