An Experimental Study on the Improvement of Durability for the Foundation Concrete under Cold Weather Condition

혹한지역 기초 콘크리트의 내구성 향상을 위한 실험 연구

  • 우상균 (한국전력공사 전력연구원) ;
  • 송영철 (한국전력공사 전력연구원) ;
  • 김경민 (고려산업개발㈜ 연구개발실) ;
  • 한천구 (청주대학교 건축공학과)
  • Published : 2003.05.01

Abstract

The purpose of this study is to provide the optimum mix design of cold weather concrete to be placed at the foundation structures in substation. The basic performance tests including slump and slump flow, air content, compressive strength and freezing & thawing resistance were conducted for cold weather concrete by varying with W/C ratios such as 40%, 50% and 60% and air contents such as 3%, 4%, 5% and 6%. The effect on durability of concrete corresponding to the increasing amount of air content and W/C ratio was evaluated and the optimum mix design was recommended. From this study, the concrete mix design containing 6% of air content and 45% of W/C ratio is recommended for the foundation concrete of substation.