A Variation of Maximum Stress with Axial Loading in Porcelain Insulators for Transmission Line using ANSYS

ANSYS를 이용한 송전용 자기재 애자의 장력에 따른 특성 변화

  • Woo, B.C. (Korea Electrotechnology Research Institute) ;
  • Han, S.W. (Korea Electrotechnology Research Institute) ;
  • Cho, H.G. (Korea Electrotechnology Research Institute)
  • Published : 2003.05.30

Abstract

The ageing cause in many porcelain suspension insulators which occur on transmission and distribution line with dead-end stings is mechanical stress in interface between porcelain and cement materials. It is known that the principal mechanical stress which give electrical failure is the results of the displacement is due to cement growth. We studied an analysing method to find out a deformation of brittle porcelain with a thermal expansion of cement for suspension insulator. These simulation analysis and experimental results show that cement volume growths affect severely to be mechanical failure ageing. These simulation analysis and experimental results show that axial loading affects of Porcelain insulators severely to be mechanical failure ageing.

Keywords