An Effect on the Solution Crystallization Temperature Difference and Cooling Capacity of the Absorption Chiller by a Solution Cooler in the Absorber

흡수기내 용액 냉각기가 흡수식 냉동기의 용액 결정화 온도차와 냉각 용량에 미치는 효과

  • 진성민 (한양대학교 기계공학과 대학원) ;
  • 이재헌 (한양대학교 공과대학 기계공학부) ;
  • 정종수 (한국과학기술연구원 환경공정연구부)
  • Published : 2003.04.23

Abstract

The objective of the present work is to investigate an effect on the solution crystallization temperature difference and the cooling capacity of the absorption chiller by a solution cooler in the absorber. The cooling capacity of the absorption chiller can be higher, with the enhanced performance of the solution heat exchangers. But, because the solution crystallization temperature difference becomes smaller at the absorber inlet, the heat capacity of the solution heat exchangers might be limited by the danger of crystallization, which can cause the serious damages. In this paper, the heat capacity ratio of the solution cooler is defined as the ratio of the heat capacity of the solution cooler to that of the absorber. If it becomes larger in the additional type solution cooler, the solution crystallization temperature difference is augmented and the cooling capacity is also increased.

Keywords