사고각에 따른 자속구속형 전류제한기의 전류제한특성

Current Limiting Characteristics of Flux-Lock Type High-TC Superconducting Fault Current Limiter According to Fault Angles

  • 박형민 (조선대학교 전기공학과) ;
  • 임성훈 (전북대학교 공업기술연구센터) ;
  • 조용선 (조선대학교 전기공학과) ;
  • 박충렬 (전북대학교 전자정보공학부) ;
  • 한병성 (전북대학교 전자정보공학부) ;
  • 최효상 (조선대학교 전기공학과) ;
  • 현옥배 (한전전력연구원)
  • 발행 : 2004.10.15

초록

We investigated current limiting characteristics of the flux-lock type high-Tc superconcting fault current limiter(HTSC-FCL) according to fault angles. The Flux-lock type HTSC-FCL consists of primary and the secondary copper coils that are wound in parallel each other through the iron core and YBCO thin flim. In this paper, the current limiting characteristics of the flux-lock type HTSC-FCL according to fault angles in case of the subtractive and additive polarity windings were compared and analyzed. From the results, the flux-lock type HTSC-FCL could limit more quickly fault current as the fault angles increased irrespective of the fault angles. On the other hand, the initial power burden of HTSC element after a fault happened increased as the fault angles increased. In addition, it was confirmed that the resistance of flux-lock type HTSC-FCL in case of subtractive polarity winding was more increased than that of additive polarity winding and that the peak current of fault current in case of subtractive polarity winding was larger than that of the additive polarity winding case.

키워드