Analysis of Simulation Results for Secondary Arc in 765kV single transmission line

765kV 1회선 선로의 2차아크 모의결과 분석

  • Published : 2004.11.12

Abstract

In many countries, including Korea, in order to transmit the more electric power, the higher transmission line voltage is inevitable. So, a rapid reclosing scheme is important for UHV transmission lines to ensure requirements for high reliability of main lines. But, because of the high voltage and long span of UHV lines, the secondary arc current flows across the fault point even after the interruption of the fault current. i.e. A critical aspect of reclosing operation is the extinction of the secondary arc since it must extinguish before successful reclosure can occur. In Korea transmission lines, it is scheduled to energize 765kV single transmission line(79km) between Sin-Ansung S/S and Sin-Gapyeong S/S at June 2006. Therefore this paper analyzes characteristics of the secondary arc extinction on 765kV single transmission line using EMTP. Simulation results shows that the average value of the secondary arc is $30A_{rms}$ and the auto-extinction time of it is longer at closer point to Sin-Gapyeong S/S.