The recent advancement in the power electronic technique has increased the use of induction motor fed by inverter using high-frequency switching devices. Also the tendency is toward larger size and higher voltage. Therefore, The IGBT (Insulated-Gate Bipolar Transistor) that is high switching frequency element has been using increase. But, The switching surge voltage was occurred by high switching frequency of inverter has appeared a voltage doubling in the motor input terminal due to mismatching of cable characteristic impedance and motor characteristic impedance. Actually, The Switching surge voltage became the major cause to occur the insulation failure by serious voltage stress in the stator winding of induction motor. The short during rise time of switching surge and cable length is increased, the maximum transient voltage seen at the motor terminals increases. In this paper, Analyzed switching surge transient voltage of power cable pulling is used EMTP(Electromagnetic Transient Program) at the induction motor terminal and in cable.