A Study on the Harmonic Resonance during Restoration of Primary Restorative Transmission System

부하투입이 고조파 공진에 미치는 영향에 대한 고찰

  • Lee, H.J. (Dept. of Electrical Engineering KwangWoon University) ;
  • Lee, K.S. (Dept. of Electrical Engineering KwangWoon University) ;
  • Park, S.M. (Dept. of Electrical Engineering KwangWoon University) ;
  • Yu, W.K (Dept. of Electrical Engineering KwangWoon University)
  • Published : 2004.11.12

Abstract

Harmonic resonant overvoltage during restoration of primary restorative transmission system originates in switching operations and nonlinear characteristics of equipments. Actually it is difficult to predict the occurrence of harmonic overvoltage, since they result from nonlinear characteristics of transformers and other equipments. This paper describes the analysis of domestic primary restorative transmission system using PSCAD/EMTDC. The harmonic resonance is verified and showed the relation with equipments which have nonlinear characteristics such as generator and transformer in this paper. And the solution to prevent harmonic resonance is proposed too. As a result, the PSCAD/EMTDC simulation showed slightly conflictive results that had been presented by IEEE Power System Restoration Working Group report.