The optical CT output signal characteristic according to temperature change

온도변화에 따른 광CT의 출력 특성

  • Published : 2004.05.07

Abstract

In this paper, we took the basic experiment in order to explore the characteristics of optical CT(optical current transformer) for measuring high current in a superhigh voltage condition using faraday effect and wrote that. We used the 1,310[nm] Laser Diode for the source of light and PIN-Photodiode for receiver. The transmission line of light was composed of the single-mode fiber of 30[m] which could maintain the state of polarization in the optical fiber. The range of current was from 400[A] to 1300[A]. In addition, the temperature ranged from $20[^{\circ}C}]\;to\;50[^{\circ}C]$. In a same experiment condition, a power magnitude increases in proportion as input current is increasing and temperature become low. The maximum ratio of error in temperature of $50[^{\circ}C]$ appears 0.15[%] and the 0.16[%], 1.24[%] and 0.07[%] is ratio of error in respectively $40[^{\circ}C],\;30[^{\circ}C],\;and\;20[^{\circ}C]$.

본 논문에서는 패러데이 효과(Faraday effect)를 이용한 초고압 전력설비에서의 대전류 측정을 위한 광CT의 특성에 대한 기초 연구를 기술하였다. 1310[nm] Laser Diode를 광원으로 사용하고 PIN-Photodiode를 수신부로 사용하였다. 광의 전송로는 파이버 내에서 편광상태를 유지 할 수 있는 30[m]의 싱글모드 파이버를 사용하였다. 전류의 측정은 400[A]에서 1300[A]까지의 범위에서 측정하였으며 온도는 $20[^{\circ}C]$에서 $50[^{\circ}C]$까지 측정하였다. 동일한 실험 환경 하에서 출력의 크기는 인가전류가 증가할수록, 온도가 낮을수록 비례하여 증가하였다. 온도가 $50[^{\circ}C]$의 경우 최대 $50[^{\circ}C]$의 오차율을 나타냈으며, $40[^{\circ}C],\;30[^{\circ}C],\;20[^{\circ}C]$의 경우 각각 최대 오차 0.16[%], 1.24[%], 0.07[%]의 오차율을 보였다.