A Basic Study on the Measurement Induced Voltages due to Lightning Discharges

뇌방전에 의한 유도전압의 측정에 대한 기초적 연구

  • 이복희 (인하대 차세대고전압전력기술연구센터) ;
  • 조성철 (인하대 차세대고전압전력기술연구센터) ;
  • 엄주홍 (기초전력연구원) ;
  • 이우철 (인하대 차세대고전압전력기술연구센터)
  • Published : 2004.05.07

Abstract

This paper deals with the device for measuring the time-varying magnetic fields and induced voltages caused by lightning discharges. The two magnetic field measuring systems were designed and made. One consists of the loop-type magnetic field sensor with the active integrator operated by a differential amplifier. The other consists of the loop-type magnetic field sensor and Labview software. The loop-type magnetic field sensor detects the time derivative of the magnetic field being measured, and the signal detected is integrated by the Labview software. As a consequence, from the calibration experiments, the frequency bandwidth of the full measuring system ranges from 400 [Hz] to 1 (MHz) and the response sensitivity are 0.98 (mV/nT) and 22 (mV/nT) for the magnetic field sensor of 2 turns and 6 turns, respectively. Also, the results obtained by the two measuring devices well agreed with each other.

Keywords