The Measurement of the Grounding Resistance Using the Ground Current of the Distribution System

접지선 전류를 시험 전류원으로 활용한 접지저항 측정기법에 관한 연구

  • Published : 2004.11.03

Abstract

Public utilities adopt the grounding rules ; class I, class II, class III and special class III, and install the grounding electrodes in distribution facilities. To keep the safety of the human and the facilities, Public utilities also manage the value of ground resistance in distribution system biennially. At present the Hook-On meter is normally used to measure the ground resistance although it has ${\pm}5[%]$ measuring error and it can not measure the exact value when the current is over 1[A]. In addition it is very difficult to use the fall-of-potential method in distribution system. In this paper we propose the new measurement method using ground current of distribution system as the current source.

Keywords