Enhancement of Power Rating for the Resistive Fault Current Limiter

병렬우선 직렬연결된 YBCO박막형 초전도 한류기의 용량증대

  • Park K.B. (ELECTROTECHNOLOGY R&D CENTER, LG Industrial Systems) ;
  • LEE B.W. (ELECTROTECHNOLOGY R&D CENTER, LG Industrial Systems) ;
  • Kang J.S. (ELECTROTECHNOLOGY R&D CENTER, LG Industrial Systems) ;
  • Oh I.S. (ELECTROTECHNOLOGY R&D CENTER, LG Industrial Systems) ;
  • hyun O.B. (KEPRI)
  • Published : 2004.07.14

Abstract

The series and parallel connection is essential for increasing power ratings of resistive type for fault current limiters. To increase voltage class, components are connected in series and to increase current level to the nominal value, they are connected in parallel. There are two ways to connect components in series and parallel. First, connected in series and then the module connects to the parallel. Second, connected in parallel and the module connects to the series. We have studied for the two ways. In this paper, we particularly investigated way to connect components in parallel first This way has the advantage of inducing effective simultaneous quench without any other devices, for example, the thing which is inducing magnetic field to the limiting and shunt resistors. And also we studied for the endurance of component which is patterned to the bi-spiral for prospective fault current. It is very important to understand this, because SFCL will use as the only device to decrease burden of circuit breaker. As experimental results, limiting component patterned to bi-spiral endures fault current up to 30kA and it works well, in parallel to series connection,