Comparison of the first and the second order eigenvalue sensitivity coefficients affected by generator modeling

발전기 모델링 정도에 의한 고유치 일차${\cdot}$이차 감도계수 비교

  • Kim Deok Young (School of Electronic & Information Engineering, Kunsan National University)
  • 김덕영 (군산대학교 전자정보공학부)
  • Published : 2004.07.14

Abstract

In small signal stability analysis of power systems, eigenvalue analysis is the most useful method and the detailed modeling of generator has an important effect to the eigenvalues. Generator full model is used for precise dynamic analysis of generators and controllers while two-axis model is used for multi-machine systems because of the reduced order of the state matrix. Also, the eigenvalue sensitivity coefficients are used for optimizing controller parameters to improve system stability. This paper compare the first and second order eigenvalue sensitivity coefficients of controllers using generator full model with those of two-axis model. As a result of an example, the estimated eigenvalues using the first and the second eigenvalue sensitivity coefficients using generator full model is very close to those of state matrix. Also the error ratios throughout a wide range of controller parameters is less than $1\%$.

Keywords