A New Distance Relaying Algorithm for Phase-to-Ground Fault in 765kV Untransposed Transmission Lines

765kV 비연가 송전선로에서 단상지락고장 시어 거리개전 알고리즘

  • 안용진 (유호전기공업(주)) ;
  • 강상희 (명지대 차세대전력기술연구센터)
  • Published : 2004.07.14

Abstract

An accurate digital distance relaying algorithm which is immune to reactance effect of the fault resistance and the load current for phase-to-ground fault in 765kV untransposed transmission lines is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the magnitude and phase of the apparent impedance, this algorithm uses the angle of an impedance deviation vector. The impedance correction algorithm for Phase-to-ground fault uses a voltage equation at fault point to compensate the fault current at fault point. A series of tests using EMTP output data in a 765kV untransposed transmission lines have proved the accuracy and effectiveness of the proposed algorithm.