Study on the application of antenna method for the criterion test of insulator arc resistance

절연체의 내아크성 평가를 위한 안테나 기법의 적용에 관한 연구

  • Published : 2004.05.21

Abstract

Electrical arc is the final stage of insulation breakdown and has high current density which cause heat and light in insulator. Insulator under electrical arc lost its insulating strength and eternal damages. Conventional criterion of electrical arc resistance in Standards have depended on the change of sound pressure and light color after damages on insulator by electrical arc. The recognition of these changes is done by human himself which was very subjective and resulted in some error to judge whether insulator has damages or not. This paper has shown that antenna method is the appropriate measure to judge electrical arc resistance for insulator. Antenna measures the electromagnetic waves radiated from tungsten electrodes with 6mm gap regulated by KSC2130. Applied voltage cross two tungsten electrodes have two different methods such as 1/8 10 and continuous 10mA. Signal amplitudes obtained by antenna has diminished after the damage of insulator, which will provide objective and good way to judge the electrical arc resistance.