The Cross Section Analysis CSA based on the Short Circuit Conditions of the Low Voltage Bare Wires

저압용 나전선의 단락조건에 의한 단면 분석

  • Published : 2005.07.18

Abstract

In this paper, we studied the cross section analysis based on the short circuit conditions of the low voltage bare wires. The copper wires prepared for the experiment were 1.2mm 1.6mm and 2.0mm in diameter. Through the cross section analysis(CSA), it was confirmed that the dendrite structure grew at the angle of about $40^{\circ}$ or $60^{\circ}$ when the fusing current was applied to the wires. The larger the fusing current is, the more decreased the growth angle of the dendrite structure is. It was confirmed that the dendrite structure was arranged like the columnar structure. In this paper, the characteristics analysis of short circuit was carried out in the range of transient duration.