Abstract

This paper presents a framework for determining control strategies against unwanted tripping actions of relay operation that plays a very important role in cascading events leading to voltage collapse. The framework includes an algorithm for quick identification of possible zone 3 relay operation during voltage instability. The proposed approach comes up with control strategy of load shedding at the selected location with active power and relay margin criteria. In addition, Quasi Steady-State (QSS) simulation is employed to obtain time-related information which is valuable for both the timing and amount of control. The methodology is demonstrated through the modified New England 39-bus system.

Keywords