Application of a Digital PSS to 220MVA Pumped Storage Unit and Its Validation Using Real-Time Digital Simulator

청평양수 발전기의 PSS 파라메터 튜닝 및 시뮬레이터를 이용한 성능검증

  • 신정훈 (한국전력공사 전력연구원) ;
  • 김태균 (한국전력공사 전력연구원) ;
  • 추진부 (한국전력공사 전력연구원) ;
  • 백영식 (경북대학교 전자전기공학부)
  • Published : 2005.07.18

Abstract

This paper describes practical tuning methods and testing of a digital PSS, which uses both frequency and power, with the 220MVA Chungpyung P/P #1 in the KEPCO system to enhance the damping of local modes. In the first step, the objective phase of PSS is computed through a phase leading function to provide compensation between the exciter reference point and the generator air-gap torque before tuning the PSS's time constants. In addition, eigenvalue analysis was used to determine a range of PSS's gain, whichis the more useful for field testing rather than a single gain value. The Real-Time Digital Simulator was used to verify safe operations of the PSS in the presence of disturbances, such as AVR step and three phase fault.

Keywords