Small signal stability analysis of oscillations caused by switching operations of SVC

SVC의 스위칭 동작에 의해 발생되는 진동현상의 미소신호 안정도 해석

  • Kim, Deok-Young (School of Electronic & Information Engineering, Kunsan National University)
  • 김덕영 (군산대학교 전자정보공학부)
  • Published : 2005.07.18

Abstract

A new small signal stability analysis method for eigenvalue analysis is presented. This method is called RCF method and based on the computation of the state transition equations and state transition matrix over a specified time interval that corresponds to one or some cycle operations of the system. This method is applicable to any system with or without switching elements. As an applicable example of RCF method in power system, the one machine infinite bus system connected switching SVC at generator terminal is investigated and the results proved that variations of oscillation modes after switching operations can be calculated exactly.

Keywords