접지방식이 상이한 철도배전계통의 연장급전을 위한 전기적 특성분석

Analysis of electric characteristics for extension power supply between different grounding railway distribution system

  • 정호성 (한국철도기술연구원 전기신호연구본부) ;
  • 한문섭 (한국철도기술연구원 전기신호연구본부) ;
  • 이장무 (한국철도기술연구원 전기신호연구본부) ;
  • 권삼영 (한국철도기술연구원 전기신호연구본부) ;
  • 박현준 (한국철도기술연구원 전기신호연구본부)
  • 발행 : 2005.11.01

초록

This paper presents electric characteristics analysis and safe configuration for extension power supply between existent 6.6kV ungrounded distribution system and establishment and improvement 22.9kV direct grounding distribution system. For this, we model 6.6kV ungrounded and 22.9kV direct grounding distribution system of urban underground, ground region. and rural electrical, unelectrical region using PSCAD/EMTDC and analyze voltage drop, charging current, ground and short fault through simulation. To analyze electric characteristics of extension power supply, we simulate extension power supply of overhead line of 6.6kV ungrounded system and underground line of 22.9kV direct grounding system of rural electrical region and propose operation condition for safe extension power supply through result of analysis. Characteristics of voltage drop, charging current, ground and short fault appear almost similarly with electrical characteristic of direct power supply. However, because unbalance of phases may cause relay's malfunction of ungrounded system and ground fault current of direct grounding system may demage facilities of ungrounded system, we propose safe system configuration such as impedance grounding system of neutral point.

키워드